FB49 OUT P02 : Output stage Heat Exchanger |
|
|
|
Network 1: Pre-Setting #Support.Estop_TOF(IN := "DI MAIN GLB".P00.GLB_Estop, PT := t#1000ms); |
|
|
|
Network 1: Call manual operation #MANUAL(ST_MANU := "DI MAIN GLB".P00.ManuCmpltMa_run, MODULE_HP := "HMI KEY".P02.GLB.F20_HomPos, SUPPORT_SEQ := "DI MAIN P02".M02.HomPosRun); |
|
|
|
Network 3: G220C Heating cycle pump 0-100% // Execute reference point #G220C.DRV.MC_Power.StartMode := #G220C.DRV.MC_MoveVelocity.Direction := 1; #G220C.DRV.MC_MoveJog.PosCntrl := TRUE; // Halt impulse #tmp_enable_axis := "HMI KEY".P02.G220C.F12_Enable_WP; #G220C.DRV.Support.FEg_Halt_Imp := #G220C.DRV.Support.FEg_Halt AND NOT #tmp_enable_axis; #G220C.DRV.Support.FEg_Halt := #tmp_enable_axis; // Execute output stage #G220C(ENABLE := #Support.Estop_TOF.Q, HALT_01 := "HMI KEY".P02.G220C.F21_Halt OR #G220C.DRV.Support.FEg_Halt_Imp OR "DI MAIN GLB".TOF_CmpltMaOFF_Pulse.Q, MCB := "E02 G220C MCB", START_VELO := #tmp_enable_axis AND (#G220C.DRV.Support.Cmd_MovAbso AND ("DI MAIN GLB".P00.AutoCmpltMa_run OR "DI MAIN P02".M02.HomPosRun OR "DI MAIN P02".SEQ1.SSM.S.stepin) OR "HMI KEY".P02.G220C.F17_GoToAbsoPos), JOG_HP := #G220C.DRV.Support.Cmd_MovJogHP AND ("DI MAIN GLB".P00.AutoCmpltMa_run OR "DI MAIN P02".M02.HomPosRun OR "DI MAIN P02".SEQ1.SSM.S.stepin) OR #MANUAL.G220C.CmdExe_slow_fast_HP, JOG_WP := #G220C.DRV.Support.Cmd_MovJogWP AND ("DI MAIN GLB".P00.AutoCmpltMa_run OR "DI MAIN P02".M02.HomPosRun OR "DI MAIN P02".SEQ1.SSM.S.stepin) OR #MANUAL.G220C.CmdExe_slow_fast_WP, ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_REg, MODE := 0, AXIS := "+2-G220C"); |
|
|
|
Network 4: M201Product Booster pump #M201(CMD_ONOFF := FALSE, FD_BACK := "E02 M201 FdB", HALT_01 := NOT "E00 Estp FdB", MCB := "E02 M201 MCB", TIME_VAL := t#5000ms, ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, MOT_CW => "A02 M201 Main", MOT_Y => "A02 M201 Y", MOT_3E => "A02 M201 3E"); |
|
|
|
Network 5: V201 Steam inlet valve #V201(CMD_WP := FALSE, FB_HP := NOT "E02 V201 WP", FB_WP := "E02 V201 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V201 WP"); |
|
|
|
Network 6: V202 Bypass heat exchanger HE1 #V202(CMD_WP := FALSE, FB_HP := "E02 V202 HP", FB_WP := "E02 V202 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V202 WP"); |
|
|
|
Network 7: V203 Glycol inlet valve #V203(CMD_WP := FALSE, FB_HP := "E02 V203 HP", FB_WP := "E02 V203 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V203 WP"); |
|
|
|
Network 8: V204 Steam regulating valve (0-100) % "FC OUT PAW"(REQ_VALUE := #V204.Output, H_LIM := 100.0, L_LIM := 0.0, PAW_OUT => "A02 V204 OutPut":P); |
|
|
|
Network 9: V205 Glycol regulating valve (0-100) % "FC OUT PAW"(REQ_VALUE := #V205.Output, H_LIM := 100.0, L_LIM := 0.0, PAW_OUT => "A02 V205 PAW":P); |
|
|
|
Network 10: PT201 Steam inlet pressure (0-9000) mbar #PT201(PEW_IN := "E02 PT201 InPut":P, H_LIM := #PT201.Support.High_Lim, L_LIM := #PT201.Support.Low_Lim, PEW_SCALE => #PT201.Support.Out_Scale); |
|
|
|
Network 11: PT202 Glycol outlet pressure (0-1500) mbar #PT202(PEW_IN := "E02 PT202 InPut":P, H_LIM := #PT202.Support.High_Lim, L_LIM := #PT202.Support.Low_Lim, PEW_SCALE => #PT202.Support.Out_Scale); |
|
|
|
Network 12: PT203 Glycol inlet pressure (0-2500) mbar #PT203(PEW_IN := "E02 PT203 InPut":P, H_LIM := #PT203.Support.High_Lim, L_LIM := #PT203.Support.Low_Lim, PEW_SCALE => #PT203.Support.Out_Scale); |
|
|
|
Network 13: PT204 Heating cycle pressure (0-2000) mbar #PT204(PEW_IN := "E02 PT204 InPut":P, H_LIM := #PT204.Support.High_Lim, L_LIM := #PT204.Support.Low_Lim, PEW_SCALE => #PT204.Support.Out_Scale); |
|
|
|
Network 14: FIT205 Heating cycle flow (0-1000) l/h #FIT205(PEW_IN := "E02 FIT205 InPut":P, H_LIM := #FIT205.Support.High_Lim, L_LIM := #FIT205.Support.Low_Lim, PEW_SCALE => #FIT205.Support.Out_Scale); |
|
|
|
Network 15: TT206 Product outlet temperature HE3 zone 1 (0-100) 76 °C #TT206(PEW_IN := "E02 TT206 InPut":P, H_LIM := #TT206.Support.High_Lim, L_LIM := #TT206.Support.Low_Lim, PEW_SCALE => #TT206.Support.Out_Scale); |
|
|
|
Network 16: TT207 Glycol inlet temperature (-5-5) 2°C #TT207(PEW_IN := "E02 TT207 InPut":P, H_LIM := #TT207.Support.High_Lim, L_LIM := #TT207.Support.Low_Lim, PEW_SCALE => #TT207.Support.Out_Scale); |
|
|
|
Network 17: TT208 Product outlet temperature HE3 zone 2 (0-100) °C #TT208(PEW_IN := "E02 TT208 InPut":P, H_LIM := #TT208.Support.High_Lim, L_LIM := #TT208.Support.Low_Lim, PEW_SCALE => #TT208.Support.Out_Scale); |
|
|
|
Network 18: TT209 Heating cycle temperature (0-100) °C #TT209(PEW_IN := "E02 TT209 InPut":P, H_LIM := #TT209.Support.High_Lim, L_LIM := #TT209.Support.Low_Lim, PEW_SCALE => #TT209.Support.Out_Scale); |
|
|
|
Network 19: TT210 Heating cycle outlet temperature HE4 (0-110) °C #TT210(PEW_IN := "E02 TT210 InPut":P, H_LIM := #TT210.Support.High_Lim, L_LIM := #TT210.Support.Low_Lim, PEW_SCALE => #TT210.Support.Out_Scale); |
|
|
|
Network 20: TT211 Glycol outlet temperature (-5-10) °C #TT211(PEW_IN := "E02 TT211 InPut":P, H_LIM := #TT211.Support.High_Lim, L_LIM := #TT211.Support.Low_Lim, PEW_SCALE => #TT211.Support.Out_Scale); |
|