FB39 OUT P01 : Output stage Fluid Connection |
|
|
|
Network 1: Pre-Setting #Support.Estop_TOF(IN := "DI MAIN GLB".P00.GLB_Estop, PT := t#1000ms); |
|
|
|
Network 1: Call manual operation #MANUAL(ST_MANU := "DI MAIN GLB".P00.ManuCmpltMa_run, MODULE_HP := "HMI KEY".P01.GLB.F20_HomPos, SUPPORT_SEQ := "DI MAIN P01".M01.HomPosRun); |
|
|
|
Network 3: G120C Product inlet pump // Execute reference point #G120C.DRV.MC_Power.StartMode := #G120C.DRV.MC_MoveVelocity.Direction := 1; #G120C.DRV.MC_MoveJog.PosCntrl := TRUE; // Halt impulse #tmp_enable_axis := "HMI KEY".P01.G120C.F12_Enable_WP; #G120C.DRV.Support.FEg_Halt_Imp := #G120C.DRV.Support.FEg_Halt AND NOT #tmp_enable_axis; #G120C.DRV.Support.FEg_Halt := #tmp_enable_axis; // Execute output stage #G120C(ENABLE := #Support.Estop_TOF.Q, HALT_01 := "HMI KEY".P01.G120C.F21_Halt OR #G120C.DRV.Support.FEg_Halt_Imp OR "DI MAIN GLB".TOF_CmpltMaOFF_Pulse.Q, MCB := "E01 G120C MCB", START_VELO := #tmp_enable_axis AND (#G120C.DRV.Support.Cmd_MovAbso AND ("DI MAIN GLB".P00.AutoCmpltMa_run OR "DI MAIN P01".M01.HomPosRun OR "DI MAIN P01".SEQ1.SSM.S.stepin) OR "HMI KEY".P01.G120C.F17_GoToAbsoPos), JOG_HP := #G120C.DRV.Support.Cmd_MovJogHP AND ("DI MAIN GLB".P00.AutoCmpltMa_run OR "DI MAIN P01".M01.HomPosRun OR "DI MAIN P01".SEQ1.SSM.S.stepin) OR #MANUAL.G120C.CmdExe_slow_fast_HP, JOG_WP := #G120C.DRV.Support.Cmd_MovJogWP AND ("DI MAIN GLB".P00.AutoCmpltMa_run OR "DI MAIN P01".M01.HomPosRun OR "DI MAIN P01".SEQ1.SSM.S.stepin) OR #MANUAL.G120C.CmdExe_slow_fast_WP, ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_REg, MODE := 0, AXIS := "+1-G120C"); |
|
|
|
Network 4: V101 Product pumpe pressure gully safety valve #V101.LampWP := "A01 V101 WP" := "HMI KEY".P01.V101.F12_Enable_WP AND #V101.CmdExe_WP; #V101.LampHP := NOT #V101.LampWP; |
|
|
|
Network 5: V102 Product pre-condition CIP gully safety valve #V102.LampWP := "A01 V102 WP" := "HMI KEY".P01.V102.F12_Enable_WP AND #V102.CmdExe_WP; #V102.LampHP := NOT #V102.LampWP; |
|
|
|
Network 6: V103 Product pre-condition CIP gully N.O. valve #V103(CMD_WP := FALSE, FB_HP := "E01 V103 HP", FB_WP := "E01 V103 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A01 V103 WP"); |
|
|
|
Network 7: V103 Product pre-condition CIP gully N.O. valve #V104.LampWP := "A01 V104 WP" := "HMI KEY".P01.V104.F12_Enable_WP AND #V104.CmdExe_WP; #V104.LampHP := NOT #V104.LampWP; |
|
|
|
Network 8: V105 Product inlet gully valve #V105(CMD_WP := FALSE, FB_HP := "E01 V105 HP", FB_WP := "E01 V105 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A01 V105 WP"); |
|
|
|
Network 9: V106 Product inlet valve #V106(CMD_WP := FALSE, FB_HP := "E01 V106 HP", FB_WP := "E01 V106 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A01 V106 WP"); |
|
|
|
Network 10: V107 Product circulation double seat valve #V107(CMD_WP := FALSE, FB_HP := "E01 V107 HP", FB_WP := "E01 V107 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A01 V107 WP"); |
|
|
|
Network 11: V108 Product circulation seat valve above V107 "A01 V108 WP" := "HMI KEY".P01.V108.F12_Enable_WP AND #V108.CmdExe_WP; #V108.LampHP := NOT "A01 V108 WP"; |
|
|
|
Network 12: V109 Product circulation seat valve below V107 #V109.LampWP :="A01 V109 WP" := "HMI KEY".P01.V109.F12_Enable_WP AND #V109.CmdExe_WP; #V109.LampHP := NOT #V109.LampWP; |
|
|
|
Network 13: V110 Water inlet double seat valve #V110(CMD_WP := FALSE, FB_HP := "E01 V110 HP", FB_WP := "E01 V110 WP", RLS := "E00 AirPressur ok", ACK_FLT := "DI MAIN GLB".P00.FLT_CmpltMaACK_Imp, VALV_WP => "A01 V110 WP"); |
|
|
|
Network 14: V111 Water inlet seat valve below V110 #V111.LampWP := "A01 V111 WP" := "HMI KEY".P01.V111.F12_Enable_WP AND #V111.CmdExe_WP; #V111.LampHP := NOT #V111.LampWP; |
|
|
|
Network 15: PT101 Product inlet pressure (0 - 3000 mbar) #PT101(PEW_IN := "E01 PT101 InPut":P, H_LIM := #PT101.Support.High_Lim, L_LIM := #PT101.Support.Low_Lim, PEW_SCALE => #PT101.Support.Out_Scale); |
|
|
|
Network 16: FIT102 Product inlet flow (0-4800.0) l/h #FIT102(PEW_IN := "E01 FIT102 InPut":P, H_LIM := #FIT102.Support.High_Lim, L_LIM := #FIT102.Support.Low_Lim, PEW_SCALE => #FIT102.Support.Out_Scale); |
|