FB49 OUT P02 : Heating Cooling Assign output stage |
|
|
|
Network 1: Call manual operation #Manual(ST_MANU := "DI MAIN GLB".M00.ManuCmpltMa_run, MODULE_HP := "HMI KEY".P01.GLB.F20_HomPos, SUPPORT_SEQ := "DI MAIN P01".M00.HomPosRun); |
|
|
|
Network 2: Pre-Setting #Support.Estop_TOF(IN := "DI MAIN GLB".M00.GLB_Estop AND NOT "HMI KEY".P01.SCARA_3D.F9_Commissioning, PT := t#1s); #tmp_s210_z_enable := "A00 G120C_S Enable" := "A00 G120_M Enable" := "A00 S120_M1 Enable" := "A00 S120_M2 Enable" := "A00 S210_M4 Enable" := #Support.Estop_TOF.Q; #tmp_operation_mode := "DI MAIN GLB".M00.AutoCmpltMa_run OR "DI MAIN P01".M00.HomPosRun OR "DI MAIN P01".SEQ1.SSM.S.stepin; #S210_Z.res_07 := #S120_M1.res_07 := #S120_M2.res_07 := #S210_M4.res_07 := #SCARA_3D.KIN.Support.Active; #G120C_S.res_07 := NOT #CAM_DISC.CAM.Support.ReadyTo_ReStart; |
|
|
|
Network 3: M200 Heating Circulation Pump #M200(CMD_ONOFF := FALSE, FD_BACK := "E00 M200 FdBk", MCB := "E00 M200 MCB", HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop, ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, MOT_CW => "A00 M200 On"); |
|
|
|
Network 4: M201 Cooling Circulation Pump #M201(CMD_ONOFF := FALSE, FD_BACK := "E00 M201 FdBk", MCB := "E00 M201 MCB", HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop, ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, MOT_CW => "A00 M201 On"); |
|
|
|
Network 5: M202 Heating/Cooling Blower #M202(CMD_ONOFF := FALSE, FD_BACK := "E00 M202 FdBk", MCB := "E00 M202 MCB", HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop, ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, MOT_CW => "A00 M202 On"); |
|
|
|
Network 6: E200 Heating/Cooling Exchanger #E200(CMD_ONOFF := FALSE, FD_BACK := "E00 E200 FdBk", MCB := "E00 E200 CB", HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop, ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, MOT_CW => "A00 E200 On"); |
|
|
|
Network 7: RV200_PID Heating Regulating Valve #RV200_PAW(REQ_VALUE := #RV200_PID.Output, H_LIM := 100.0, L_LIM := 0.0, PAW_OUT => "A00 TC100_OUT":P); |
|
|
|
Network 8: RV200_PAW Heating Regulating Output #RV200_PAW(REQ_VALUE := #RV200_PID.Output, H_LIM := 100.0, L_LIM := 0.0, PAW_OUT => "A00 TC100_OUT":P); |
|
|
|
Network 9: V200 Heating Shut-Off Valve #V200(CMD_WP := FALSE, FB_HP := "E02 V200 CLS", FB_WP := "E02 V200 OPN", RLS := "E00 Air Pressure OK", ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V200 OPN"); |
|
|
|
Network 10: V201 Heating Secondary Circuit Shut-Off Valve #V201(CMD_WP := FALSE, FB_HP := "E02 V201 CLS", FB_WP := "E02 V201 OPN", RLS := "E00 Air Pressure OK", ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V201 OPN"); |
|
|
|
Network 11: V202 Cooling Shut-Off Valve #V202(CMD_WP := FALSE, FB_HP := "E02 V202 CLS", FB_WP := "E02 V202 OPN", RLS := "E00 Air Pressure OK", ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V202 OPN"); |
|
|
|
Network 12: V203 Cooling Shut-Off Valve #V203(CMD_WP := FALSE, FB_HP := "E02 V203 CLS", FB_WP := "E02 V203 OPN", RLS := "E00 Air Pressure OK", ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V203 OPN"); |
|
|
|
Network 13: V204 Suction Valve #V204(CMD_WP := FALSE, FB_HP := "E02 V204 CLS", FB_WP := "E02 V204 OPN", RLS := "E00 Air Pressure OK", ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp, VALV_WP => "A02 V204 OPN"); |
|
|
|
Network 14: T200_PEW Hot Water E200 Input Temperature 0.0-120.0°C #T200_PEW(PEW_IN := "E00 T100_PEW":P, H_LIM := #T200_PEW.Support.High_Lim, L_LIM := #T200_PEW.Support.Low_Lim, PEW_SCALE := #T200_PEW.Support.PEW_Scaled); |
|
|
|
Network 15: T201_PEW Hot Water E200 Output Temperature 0.0-115.0°C #T201_PEW(PEW_IN := "E00 T100_PEW":P, H_LIM := #T201_PEW.Support.High_Lim, L_LIM := #T201_PEW.Support.Low_Lim, PEW_SCALE := #T201_PEW.Support.PEW_Scaled); |
|
|
|