FB49 OUT P02 : Heating Cooling Assign output stage

[hit  <- on your browser to return]

 

 

 

Network 1: Call manual operation

#Manual(ST_MANU := "DI MAIN GLB".M00.ManuCmpltMa_run,

        MODULE_HP := "HMI KEY".P01.GLB.F20_HomPos,

        SUPPORT_SEQ := "DI MAIN P01".M00.HomPosRun);

 

 

 

Network 2: Pre-Setting

#Support.Estop_TOF(IN := "DI MAIN GLB".M00.GLB_Estop AND NOT "HMI KEY".P01.SCARA_3D.F9_Commissioning,

                   PT := t#1s);

#tmp_s210_z_enable := "A00 G120C_S Enable" := "A00 G120_M Enable" := "A00 S120_M1 Enable" := "A00 S120_M2 Enable" := "A00 S210_M4 Enable" := #Support.Estop_TOF.Q;

#tmp_operation_mode := "DI MAIN GLB".M00.AutoCmpltMa_run OR "DI MAIN P01".M00.HomPosRun OR "DI MAIN P01".SEQ1.SSM.S.stepin;

#S210_Z.res_07 := #S120_M1.res_07 := #S120_M2.res_07 := #S210_M4.res_07 := #SCARA_3D.KIN.Support.Active;

#G120C_S.res_07 := NOT #CAM_DISC.CAM.Support.ReadyTo_ReStart;

 

 

 

Network 3: M200 Heating Circulation Pump

#M200(CMD_ONOFF := FALSE,

      FD_BACK := "E00 M200 FdBk",

      MCB := "E00 M200 MCB",

      HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop,

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      MOT_CW => "A00 M200 On");

 

 

 

Network 4: M201 Cooling Circulation Pump

#M201(CMD_ONOFF := FALSE,

      FD_BACK := "E00 M201 FdBk",

      MCB := "E00 M201 MCB",

      HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop,

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      MOT_CW => "A00 M201 On");

 

 

 

Network 5: M202 Heating/Cooling Blower

#M202(CMD_ONOFF := FALSE,

      FD_BACK := "E00 M202 FdBk",

      MCB := "E00 M202 MCB",

      HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop,

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      MOT_CW => "A00 M202 On");

 

 

 

Network 6: E200 Heating/Cooling Exchanger

#E200(CMD_ONOFF := FALSE,

      FD_BACK := "E00 E200 FdBk",

      MCB := "E00 E200 CB",

      HALT_01 := NOT "DI MAIN GLB".M00.GLB_Estop,

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      MOT_CW => "A00 E200 On");

 

 

 

Network 7: RV200_PID Heating Regulating Valve

#RV200_PAW(REQ_VALUE := #RV200_PID.Output,

           H_LIM := 100.0,

           L_LIM := 0.0,

           PAW_OUT => "A00 TC100_OUT":P);

 

 

 

Network 8: RV200_PAW Heating Regulating Output

#RV200_PAW(REQ_VALUE := #RV200_PID.Output,

           H_LIM := 100.0,

           L_LIM := 0.0,

           PAW_OUT => "A00 TC100_OUT":P);

 

 

 

Network 9: V200 Heating Shut-Off Valve

#V200(CMD_WP := FALSE,

      FB_HP := "E02 V200 CLS",

      FB_WP := "E02 V200 OPN",

      RLS := "E00 Air Pressure OK",

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      VALV_WP => "A02 V200 OPN");

 

 

 

Network 10: V201 Heating Secondary Circuit Shut-Off Valve

#V201(CMD_WP := FALSE,

      FB_HP := "E02 V201 CLS",

      FB_WP := "E02 V201 OPN",

      RLS := "E00 Air Pressure OK",

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      VALV_WP => "A02 V201 OPN");

 

 

 

Network 11: V202 Cooling Shut-Off Valve

#V202(CMD_WP := FALSE,

      FB_HP := "E02 V202 CLS",

      FB_WP := "E02 V202 OPN",

      RLS := "E00 Air Pressure OK",

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      VALV_WP => "A02 V202 OPN");

 

 

 

Network 12: V203 Cooling Shut-Off Valve

#V203(CMD_WP := FALSE,

      FB_HP := "E02 V203 CLS",

      FB_WP := "E02 V203 OPN",

      RLS := "E00 Air Pressure OK",

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      VALV_WP => "A02 V203 OPN");

 

 

 

Network 13: V204 Suction Valve

#V204(CMD_WP := FALSE,

      FB_HP := "E02 V204 CLS",

      FB_WP := "E02 V204 OPN",

      RLS := "E00 Air Pressure OK",

      ACK_FLT := "DI MAIN GLB".M00.FLT_CmpltMaACK_Imp,

      VALV_WP => "A02 V204 OPN");

 

 

 

Network 14: T200_PEW Hot Water E200 Input Temperature 0.0-120.0°C

#T200_PEW(PEW_IN := "E00 T100_PEW":P,

          H_LIM := #T200_PEW.Support.High_Lim,

          L_LIM := #T200_PEW.Support.Low_Lim,

          PEW_SCALE := #T200_PEW.Support.PEW_Scaled);

 

 

 

Network 15: T201_PEW Hot Water E200 Output Temperature 0.0-115.0°C

#T201_PEW(PEW_IN := "E00 T100_PEW":P,

          H_LIM := #T201_PEW.Support.High_Lim,

          L_LIM := #T201_PEW.Support.Low_Lim,

          PEW_SCALE := #T201_PEW.Support.PEW_Scaled);

 

 

 

Network 16: T202_PEW Cold Water E200 Output Temperature 0.0-100.0°C

#T202_PEW(PEW_IN := "E00 T100_PEW":P,

          H_LIM := #T202_PEW.Support.High_Lim,

          L_LIM := #T202_PEW.Support.Low_Lim,

          PEW_SCALE := #T202_PEW.Support.PEW_Scaled);